Façade defects · Fire risk

Spandrel panel defects: insulation, condensation and glass.

The opaque panels between floors in curtain walling hide the slab edge, insulation and fire stopping. What goes wrong behind them.

MTC defects libraryFire risk in external wallsUpdated November 2026
At a glance
What it isProblems with the opaque panels in curtain walling or window systems that cover floor zones.
Main riskCombustible insulation, missing slab-edge fire stopping, condensation and glass breakage.
Common onCurtain-walled offices, hotels and apartment blocks.
Usually spotted byFRAEWs, condition surveys and occupants noticing misting or broken glass.

Misting, staining or broken spandrels? We open up and record spandrel zones as part of a FRAEW or a defect investigation. See our façade defect investigations or contact us for a quote. If the problem is already in dispute, our façade expert witness service can help.

What a spandrel panel is

A spandrel panel is the opaque part of a curtain wall or window system, usually in front of a floor slab or downstand. It can be coloured glass, a glass shadow box with a gap behind, a metal panel or an insulated composite panel. Behind it sits insulation, a back pan and, at the slab edge, fire stopping.

How to recognise it

  • Misting, condensation or staining visible behind glass spandrels.
  • Cracked or broken spandrel glass.
  • Bowing, delamination or blistering of metal or composite panels.
  • Water marks on the slab edge or ceiling below.
  • No records of the insulation or back pan behind the panels.

Why it happens

  • Combustible insulation used behind the panel.
  • Shadow boxes not vented or sealed as designed, so moisture collects.
  • Heat build-up behind dark glass causing thermal stress cracks.
  • Failed seals letting water into the panel.
  • Slab-edge fire stopping left out behind the panel.

Why it matters

  • Fire safety. Insulation and back pans behind spandrels form part of the external wall and are appraised under PAS 9980.
  • Fire spread between floors if the slab-edge fire stopping is missing. See fire stopping.
  • Falling glass from broken spandrels. See glass breakage.

How we investigate it

We remove sample spandrel panels, internally where possible, to record the panel, insulation, back pan, slab-edge fire stopping and fixings. Condensation and leaks are traced with water testing and, where useful, thermography. See thermographic surveys.

How it is put right

  • Replace combustible insulation with non-combustible products.
  • Install or repair slab-edge fire stopping.
  • Re-seal or re-vent shadow boxes.
  • Replace broken or delaminated panels to the system's details.

See our published case studies

What to send us

The address, the building's height, any curtain walling drawings or O&M manuals, and photos of misting, staining or breakage. Email enquiries@mtconsult.co.uk, use our contact form or call 0800 048 5229. We typically respond within one working day.

Frequently asked questions

Why is there condensation behind my spandrel glass?

Usually the shadow box behind it is not sealed or vented as designed, or a seal has failed.

Do spandrel panels count in a FRAEW?

Yes. The insulation and materials behind them are part of the external wall.

Can spandrels be inspected from inside?

Often, yes. Sample panels can usually be accessed from inside the building, avoiding external access.