Façade defects · Fire risk

Missing or poor fire stopping: slab edges and penetrations.

Where fire stopping is needed in and around external walls, what goes wrong, and how surveys find gaps before a fire does.

MTC defects libraryFire risk in external wallsUpdated November 2026
At a glance
What it isGaps, wrong products or poor installation where fire stopping should seal a compartment line.
Main riskFire and smoke spreading between floors or flats.
Common onCurtain-walled offices and apartments, and any building where services pass through compartment walls and floors.
Usually spotted byCompartmentation surveys, FRAEWs, fire risk assessments and refurbishment works.

Seeing gaps at slab edges or penetrations? Our compartmentation surveys open up, record and report on every sample location. See our compartmentation surveys or contact us for a quote. If the problem is already in dispute, our façade expert witness service can help.

Fire stopping and cavity barriers

Fire stopping seals gaps where a compartment wall or floor meets something else, or where pipes, cables and ducts pass through it. Cavity barriers do a different job: they close the hidden cavity inside an external wall. Both are needed, and they often meet at the slab edge. See missing cavity barriers.

How to recognise it

  • A visible gap between the floor slab and curtain walling or cladding.
  • Service penetrations packed with foam, or left open.
  • Fire-stopping products with no labels or installation records.
  • Fire stopping disturbed by later cabling or alterations.
  • Daylight or draughts between floors at the façade line.

Why it happens

  • Slab-edge fire stopping left out because it sits behind ceilings and finishes.
  • Products used outside their tested arrangement.
  • Trades cutting through compartment lines after the fire stopping is installed.
  • No one trade responsible for the interface between façade and floor.
  • Missing or vague drawings and specifications.

Why it matters

  • Fire spread. A gap at the slab edge can let fire and smoke move up the inside face of the façade.
  • Compliance. Compartmentation is a key part of the fire strategy and the fire risk assessment.
  • Building safety case. On higher-risk buildings, the accountable person needs evidence that compartmentation works.

How we investigate it

We open ceilings, linings and floor voids at sample locations, record each penetration and slab-edge detail with photos, and check products against their test evidence. Where the façade is being appraised under PAS 9980, the same openings record the slab-edge detail for the FRAEW. See our compartmentation surveys.

How it is put right

  • Install tested slab-edge fire stopping to match the façade system.
  • Replace foam and unlabelled products with tested systems.
  • Label and record every penetration seal.
  • Put a permit system in place so later trades do not breach compartment lines.

See our published case studies

What to send us

The address, the building's height and use, any fire strategy or fire risk assessment, and photos of anything you are concerned about. Email enquiries@mtconsult.co.uk, use our contact form or call 0800 048 5229. We typically respond within one working day.

Frequently asked questions

What is the difference between fire stopping and a cavity barrier?

Fire stopping seals gaps in and around compartment walls and floors. Cavity barriers close the cavity inside an external wall. Both are needed.

Is expanding foam fire stopping?

Only specific tested fire-rated foams, used as tested. General-purpose foam is not fire stopping.

Can fire stopping be checked without opening up?

Rarely. It is usually hidden behind ceilings and linings, so sample openings are needed.

Related

Talk to us

Worried about fire stopping?

Our in-house contracting team provides the access and opening-up, so you have one point of contact.

© McKay Turner Consulting LtdFaçade defects · Missing or poor fire stopping